Texnik xususiyatlar va parametrlar:
| Turni belgilash | SiH-10KWTH-PRO | SiH-12kW-TH | SiH-15kW-TH | SiH-20kW-TH | SiH-25kW-TH | SiH-30kW-TH |
| PV(kiritish) | ||||||
| Tavsiya etilgan maksimum PV kirish quvvati | 20000Wp | 24000Wp | 30000Wp | 40000Wp | 50000Wp | 60000Wp |
| Maksimum PV kirish voltaji | 1000V | |||||
| Nominal PV kirish qarzlari | 650V | |||||
| MPP qarz diapazoni | 150V-950V | |||||
| MPPT soni / har bir MPPT uchun strings | 3 (1/1/1) | 3(1/1/1) | 3 (2/1/1) | 3 (2/2/1) | 3(2/2/2) | |
| Maks. PV elektr ichki jarayon(PV1/PV2 /PV3) | 48A(16A/16A/16 A) | 64A(32A/16A/16 A) | 80A(32A/32A/16A) | 96A(32A/32A/32A) | ||
| Maks. qisqacha uyuzma elektr ichki jarayon(PV1 /PV2 /PV3) | 60A(20A/20A/20A) | 80A(40A/20A/20A) | 100A(40A/40A/20A) | 120A(40A/40A/40A) | ||
| Аккумулятор ( kirish/chiqish ) | ||||||
| Batareya Turi | Li-ion akkumulyator | |||||
| Batareya voltaj oralig'i | 100V-800V | |||||
| Maksimal yuklash /bosuv to'kichi | 50A/50A* | |||||
| Maksimal yuklash /bosuv quvvati | 15000W/10000W | 15000W/12000W | 30000W/15000W | 30000W/20000W | 30000W/25000W | 30000W/30000W |
| Tarmoq (kirish/chiqish) | ||||||
| Tizimdan olinadigan maksimal AC quvvati | 43000W/43000VA | |||||
| Nominal AC chiqish quvvati | 10000VA | 12000VA | 15000VA | 20000VA | 25000VA | 30000VA |
| Maksimal AC chiqish quvvati | 10000VA | 12000VA | 15000VA | 20000VA | 25000VA | 30000VA |
| Maks. Oʻzgaruvchan chiqish oqimi | 15.2A | 18.2A | 22.8A | 30.4A | 37.9A | 45.5A |
| Nominal o'zgaruvchi kuchlanmasi | 3/N/PE,220/380V;230/400V;240/415 V | |||||
| Oʻzgaruvchan kuchlanuvchanlik oraligʻi | 270V-480V | |||||
| Nominal tarmoq chastotasi | 50Hz/60Hz | |||||
| Tarmoq chastotalari oralig'i | 45Hz-55Hz/55Hz-65Hz | |||||
| THDi (Nomal quchi) | <3% (nomal quchi) | |||||
| Koʻrsatki nomal quchida / Oʻrnatib boriladigan quvvat koeffitsiyenti |
>0.99 /0.8 oldindan 0.8 orqaga | |||||
| Yozma (chiqim) | ||||||
| Nominal kuchlanmasi | 3/N/PE.220V;230V;240 V | |||||
| Chastota diapazoni | 50Hz/60Hz | |||||
| THDv (Nominal quvvat, Liney yuk) | 2% | |||||
| Yozma almashtirish vaqti | <10mS | |||||
| Tarmoqdan tashqarida bo'lgan holatdagi nominal chiqim quvvati | 10000VA | 12000VA | 15000VA | 20000VA | 25000VA | 30000VA |
| Tarmoqdan tashqarida bo'lgan holatdagi maksimal chiqim quvvati** | 15000W/15000VA 10 sekundlar |
16800W/168000VA 10 sekundlar |
25500W/25500VA 10 sekundlar |
32000W/32000VA 10 sekundlar |
36500W/36500VA 10 sekundlar |
45000W/45000VA 10 sekundlar |
| Max. rezerv rejimida chiqish quvvati tizimda ishlash rejimida yuk |
43000W/43000VA | |||||
| Max. rezerv rejimida chiqish to'kimi tizimda ishlash rejimida yuk |
3*63A(25°C) | |||||
| Ish samaradorligi | ||||||
| Maksimal effektivlik / Evropiy effektivlik | 98.0%/97.5 % | 98.1 %/97.6 % | 98.2%/97.8% | |||
| Umumiy ma'lumotlar | ||||||
| O'lchamlar (W*H*D) | 615 мм*460 мм*245 мм | |||||
| Og'irlik | 34kg | 35kg | 36kg | |||
| Montaj usuli | Divarli o'rnatish stoyki | |||||
| Topologiya (Sollar/Akkumulyator) | Трансформаторсиз/Трансформаторсиз | |||||
| Himoya darajasi | IP65 | |||||
| Ishga tushiruvchi atrof muhit harorati oralig'i | -25°C~60°C, 45 °C pastida ретга йўқ | |||||
| Ruxsat etilgan nisbiy namlik oralig'i (Янгилашмас) |
0~100% | |||||
| Suzilish usuli | Tabiiy konveksiya | Вентилятор ўртириш | ||||
| Maksimal operatsion balandlik | 2000m | |||||
| Дисплей | LED | |||||
| Aloqa | 2xRS485,WLAN,2 xCAN | |||||
| DI/DO | 4xDI,1xDO,DRMO | |||||
| To'g'ri oqimli ulangan tarmoq turi | MC4 (PV, Макс. 6mm²) Плагин ва плей коннектор (батарея, Макс.10mm²) | |||||
| AC ulanish turi | OT Терминали(жорий /дастугун,Макс.20mm²) | |||||
Mahsulot xususiyatlari:
OUTSTANDING PERFORMANCE.
МаX.50A батарея ўтказиш ва ўтказиш дизайни
200% Dc kirish o'rnatilgan
Uch fazali asimetrik chiqish
100% dan pastdagi no'muvofiq yuklarda
MURAKKABLI QULLANISH.
Ko'p parallel ulanishni qollab-quvvatlaydi
Bir fazali elektr energiyasi chiqish rejiini qollab quvatlash
100~800V keng batteriya voltaj diapazoni
SUPERB OFF-GRID LOAD.
Butun uy uchun rezerv
Yarim dalda ishlash va to'q bo'lgan yukni qollab-quvvatlaydi
<10mS off-grid o'tish
QIZIQARLI DIZAYN.
≤ 36KG, yengilroq o'rnatish
Chizish dizayni, ventilyatorsiz dizayn, past ziyorat
AFCI ni qollaydi
Uzaktan xatolarni aniqlash va dastur yangilanishi